Top

H10F35 (32A-63A) 500Vacdc fast fuse

H10F35 (32A-63A) 500Vacdc fast fuse

H10F35 (32A-63A) 500Vacdc fast fuse

This series of fuses are suitable for rated DC (AC) 500V (32A-63A) line protection, as instrument power supply, uninterruptible UPS power supply, three-phase AC charging pile, electric vehicle supply equipment (EVSE) inverter, rectifier, motor, elevator and other systems and other comprehensive protection, but also has the characteristics of strong current limiting ability, high breaking capacity, short circuit breaking speed, and can withstand temperature shock, mechanical shock, current shock, chemical load, etc. Breaking capacity: 20KA. Reference technical standard UL248-1.

Description

This series of fuses are suitable for rated DC (AC) 500V (32A-63A) line protection, as instrument power supply, uninterruptible UPS power supply, three-phase AC charging pile, electric vehicle supply equipment (EVSE) inverter, rectifier, motor, elevator and other systems and other comprehensive protection, but also has the characteristics of strong current limiting ability, high breaking capacity, short circuit breaking speed, and can withstand temperature shock, mechanical shock, current shock, chemical load, etc. Breaking capacity: 20KA. Reference technical standard UL248-1.

              H10F35 EVSEFast fuse

1.Purpose and use

The series fuse is suitable for rated DC(AC)500V (32A-63A) line protection, as instrument power supply, uninterrupted UPS power supply, three-phase AC charging pile, electric vehicle supply equipment (EVSE) inverter, rectifier, motor, elevator system and other comprehensive protection. It also has the characteristics of strong current limiting capacity, high breaking capacity, short circuit breaking speed, and can withstand temperature impact, mechanical impact, current impact, chemical load and so on. Breaking capacity :20KA. See technical standard UL248-1.

2.Normal working conditions

Ambient air temperature Normal use condition: -40+125℃;

3.  Use category

 fast fuse for full range protection.

4. Agreed current and agreed time

Test current

A

Fusing time s

In:

min

max

1In

14400

-

1.35In

-

3600

2In

12

360

Note: The agreed current and agreed time required by the customer can be negotiated with our company.

6. Main parameters

No:

Model number

Rated currentA)

Rated voltage

DC/ACV

Breaking capacity

DC/AC20KA

Watts Loss at 70% Rated Current (W)

Watts Loss at 100%

Rated Current (W)

6

H10F3532

32A

500V

20KA

1.16

3.5

8

H10F3540

40A

500V

20KA

1.51

3.6

10

H10F3550

50A

500V

20KA

1.78

4.35

11

H10F3563

63A

500V

20KA

2.16

5.1

Note: Can be customized according to specific requirements